Near N Beaman Ave, Kansas City 1 year ago
BRADFORD WHITE
  • Bradford White leaking from tank
  • AO Smith 64151
Model
MI40T5LN10
Rating
Feedback It worked great until it rusted through and started leaking. I hope my new one lasts as long.
Posted
1 year ago
Age
24 Years
Size
40 GALLON
Open/Closed Loop
CLOSED LOOP
Reason for Replacement
LEAK
Expansion Tank
NO
Valve Meter
NO
PRV
YES
Water Softner
NO
Installation Type
Installation
Water Pressure Inside
96 psi
Water Pressure City
96 psi
Old Description
The old water heater was 22 years old and leaking slowly from the bottom of the tank. The water heater was under 96 lbs of water pressure and was on a closed system. The water pressure was high due to the failed PRV. Other water pressure readings in the neighborhood show that the water pressure was not always that high.
New Description
AO Smith water heater installed along with thermal expansion tank and new PRV. The line for the humidifier was also replaced with a full brass body compression valve which was also lead free. The water pressure was set to 75 psi and the expansion tank was also set to 75 psi.
Feedback by Customer
Chase did a great job of explaining what we needed and in replacing our water heater in a timely manner. Thank you!